Technical Parameters |
Item |
AF-10MR-A2 |
AF-10MR-D2 |
AF-10MR-E2 |
AF-10MT-D2 |
AF-10MT-GD2 |
AF-10MT-E2
|
AF-20MR-A2
|
AF-20MR-D2
|
AF-20MR-E2
|
AF-20MT-D2
|
AF-20MT-GD2
|
AF-20MT-E2
|
Surge Immunity |
2kv(common mode), 1kv(differential mode), Level 3 (IEC61000-4-5) |
Electrostatic Discharge (outer casing) |
±8kv(air discharge)/±6kv(contact discharge), Level 3 (IEC61000-4-5) |
Ambient Temperature |
-10ºC~+55ºC |
Storage Temperature |
-40ºC~+70ºC |
Ambient Humidity |
5%~95%RH |
Degree of Protection |
IP20(Non-waterproof) |
Installation |
Fixing with M3 screws or Standard DIN rail mounting |
Dimensions (mm) |
71.6*90.4*51.3(10 points);126.4*90.4*51.3(20 points) |
Programming Language |
FBD |
Points |
10 points/20 points |
Memory Capacity |
127 FBDs |
Real-time Clock |
160h |
Password Protection |
yes |
Analog Operation |
At most 12 channels with DC 0-10V voltage |
Simulate Monitoring |
Yes |
Communication Interface |
support 2 channel with RS485 and 1 channel with program interfaces |
Baud Rate |
9600bps/19200bps |
Communication Protocol |
Self-defined protocol/MODBUS RTU protocol (only read) |
Power Supply |
Rated Voltage |
AC100-240V |
DC12-24V |
AC/DC12-24V |
DC12-24V |
DC12-24V |
DC12-24V
|
Permissible Range |
DC85-260V |
DC10-28V |
AC/DC10-28V |
DC10-28V |
DC10-28V |
DC10-28V
|
Power Consumption |
<10w
|
<7w
|
<7w
|
<2w
|
<2w
|
<2w
|
Digital Input |
Input Type |
NPN/PNP |
NPN/PNP |
NPN/PNP |
NPN/PNP |
NPN/PNP |
NPN/PNP
|
Input Signal 0 |
AC0-40V |
DC0-5V |
AC/DC0-5V |
DC0-5V |
DC0-5V |
DC0-5V
|
Input Signal 1 |
AC80-240V |
DC10-24V |
AC/DC10-24V |
DC10-24V |
DC10-24V |
DC10-24V
|
Isolation |
Photoelectric isolation |
-- |
-- |
-- |
-- |
--
|
Isolated Group |
6/12 groups |
Isolated Voltage |
2500/5000Vr.m.s |
Digital Output |
Output Type |
Relay |
Relay |
Relay |
Transistor(NPN) |
Transistor(PNP) |
Transistor(NPN) |
Isolation Method |
Relay isolation |
Relay isolation |
Relay isolation |
- |
- |
- |
Analog Input |
Input Type |
-- |
(DC0-10V)/6 inputs |
--
|
(DC0-10V)/6 inputs |
(4-20mA)/2 inputs |
-- |
(DC0-10V)/12 inputs
|
(DC0-10V)/12 inputs
|
(DC0-10V)/12 inputs
|
|
|
|
|
|
|
|
|
|
|
|
Type
|
AF-10MR-A2 |
AC100V-240V |
6 points digital input |
4 points relay output |
AF-10MR-D2 |
DC12V-24V |
6 points digital input (can be used as analog inputs) |
4 points relay output |
AF-10MR-E2 |
AC/DC12V-24V |
6 points digital input |
4 points relay output |
AF-10MT-D2 |
DC12V-24V |
6 points digital input (can be used as analog inputs) |
4 points NPN transistor output |
AF-10MT-GD2 |
DC12V-24V |
6 points digital input (can be used as analog inputs) |
4 points PNP transistor output
|
AF-10MT-E2 |
DC12V-24V |
6 points digital input |
4 points NPN transistor output |
AF-20MR-A2 |
AC100V-240V |
12 points digital input |
8 points relay output |
AF-20MR-D2 |
DC12V-24V |
12 points digital input (can be used as analog inputs) |
8 points relay output |
AF-20MR-E2 |
AC/DC12V-24V |
12 points digital input |
8 points relay output |
AF-20MT-D2 |
DC12V-24V |
12 points digital input (can be used as analog inputs) |
8 points NPN transistor output |
AF-20MT-GD2 |
DC12V-24V |
12 points digital input (can be used as analog inputs) |
8 points PNP transistor output
|
AF-20MT-E2 |
DC12V-24V |
12 points digital input |
8 points NPN transistor output |
|
Auxiliary Module |
AF-2322 |
the cable is used to read/write the program by PC 232 port |
AF-DUSB2 |
the cable is used to read/write the program by PC USB port |
AF-HMI |
The removable LCD panel |
|
|
Dimensions |
Take the 10 points module as an example. The 20 points modules share the same width and height, the only one difference exists in the length. |
|
Type |
Dimensions(mm) |
10 points main module |
71.6*90.4*51.3 |
20 points main module |
126.4*90.4*51.3 |
|
The FAB Intelligent Controller Series, proudly introduced by ARRAY, is a groundbreaking programmable controller designed to revolutionize your automation process. Utilizing the cutting-edge Function Block Diagram (FBD) programming, this innovative controller is significantly simpler and easier to master than traditional PLC programming methods like ladder diagram and instruction sets. The visionary design of the ARRAY FAB series ingeniously integrates the conventional separate PLC controller with the writer, allowing programs to be effortlessly created directly on the LCD front panel using intuitive function keys. This integration not only slashes costs but also maximizes user convenience. The ARRAY FAB is remarkably compact and lightweight, making it the perfect choice for internal installations where space and efficiency are paramount.
Furthermore, the FAB Intelligent Controller Series excels in both local and remote Internet communication and monitoring capabilities, truly setting a new standard in technological sophistication. Equipped with a versatile voice module, the FAB can effortlessly perform telephone remote control, issue voice prompts, and execute auto-dialing, among other advanced functions. Today, the ARRAY FAB is extensively utilized across diverse sectors, including industry, agriculture, and smart home automation, showcasing its incredible versatility and adaptability. Its applications are virtually limitless, making it an indispensable tool for modern automation needs.
ca47ed4a