Technical Parameters |
Item |
AF-10MR-A2 |
AF-10MR-D2 |
AF-10MR-E2 |
AF-10MT-D2 |
AF-10MT-GD2 |
AF-10MT-E2
|
AF-20MR-A2
|
AF-20MR-D2
|
AF-20MR-E2
|
AF-20MT-D2
|
AF-20MT-GD2
|
AF-20MT-E2
|
Surge Immunity |
2kv(common mode), 1kv(differential mode), Level 3 (IEC61000-4-5) |
Electrostatic Discharge (outer casing) |
±8kv(air discharge)/±6kv(contact discharge), Level 3 (IEC61000-4-5) |
Ambient Temperature |
-10ºC~+55ºC |
Storage Temperature |
-40ºC~+70ºC |
Ambient Humidity |
5%~95%RH |
Degree of Protection |
IP20(Non-waterproof) |
Installation |
Fixing with M3 screws or Standard DIN rail mounting |
Dimensions (mm) |
71.6*90.4*51.3(10 points);126.4*90.4*51.3(20 points) |
Programming Language |
FBD |
Points |
10 points/20 points |
Memory Capacity |
127 FBDs |
Real-time Clock |
160h |
Password Protection |
yes |
Analog Operation |
At most 12 channels with DC 0-10V voltage |
Simulate Monitoring |
Yes |
Communication Interface |
support 2 channel with RS485 and 1 channel with program interfaces |
Baud Rate |
9600bps/19200bps |
Communication Protocol |
Self-defined protocol/MODBUS RTU protocol (only read) |
Power Supply |
Rated Voltage |
AC100-240V |
DC12-24V |
AC/DC12-24V |
DC12-24V |
DC12-24V |
DC12-24V
|
Permissible Range |
DC85-260V |
DC10-28V |
AC/DC10-28V |
DC10-28V |
DC10-28V |
DC10-28V
|
Power Consumption |
<10w
|
<7w
|
<7w
|
<2w
|
<2w
|
<2w
|
Digital Input |
Input Type |
NPN/PNP |
NPN/PNP |
NPN/PNP |
NPN/PNP |
NPN/PNP |
NPN/PNP
|
Input Signal 0 |
AC0-40V |
DC0-5V |
AC/DC0-5V |
DC0-5V |
DC0-5V |
DC0-5V
|
Input Signal 1 |
AC80-240V |
DC10-24V |
AC/DC10-24V |
DC10-24V |
DC10-24V |
DC10-24V
|
Isolation |
Photoelectric isolation |
-- |
-- |
-- |
-- |
--
|
Isolated Group |
6/12 groups |
Isolated Voltage |
2500/5000Vr.m.s |
Digital Output |
Output Type |
Relay |
Relay |
Relay |
Transistor(NPN) |
Transistor(PNP) |
Transistor(NPN) |
Isolation Method |
Relay isolation |
Relay isolation |
Relay isolation |
- |
- |
- |
Analog Input |
Input Type |
-- |
(DC0-10V)/6 inputs |
--
|
(DC0-10V)/6 inputs |
(4-20mA)/2 inputs |
-- |
(DC0-10V)/12 inputs
|
(DC0-10V)/12 inputs
|
(DC0-10V)/12 inputs
|
|
|
|
|
|
|
|
|
|
|
|
Type
|
AF-10MR-A2 |
AC100V-240V |
6 points digital input |
4 points relay output |
AF-10MR-D2 |
DC12V-24V |
6 points digital input (can be used as analog inputs) |
4 points relay output |
AF-10MR-E2 |
AC/DC12V-24V |
6 points digital input |
4 points relay output |
AF-10MT-D2 |
DC12V-24V |
6 points digital input (can be used as analog inputs) |
4 points NPN transistor output |
AF-10MT-GD2 |
DC12V-24V |
6 points digital input (can be used as analog inputs) |
4 points PNP transistor output
|
AF-10MT-E2 |
DC12V-24V |
6 points digital input |
4 points NPN transistor output |
AF-20MR-A2 |
AC100V-240V |
12 points digital input |
8 points relay output |
AF-20MR-D2 |
DC12V-24V |
12 points digital input (can be used as analog inputs) |
8 points relay output |
AF-20MR-E2 |
AC/DC12V-24V |
12 points digital input |
8 points relay output |
AF-20MT-D2 |
DC12V-24V |
12 points digital input (can be used as analog inputs) |
8 points NPN transistor output |
AF-20MT-GD2 |
DC12V-24V |
12 points digital input (can be used as analog inputs) |
8 points PNP transistor output
|
AF-20MT-E2 |
DC12V-24V |
12 points digital input |
8 points NPN transistor output |
|
Auxiliary Module |
AF-2322 |
the cable is used to read/write the program by PC 232 port |
AF-DUSB2 |
the cable is used to read/write the program by PC USB port |
AF-HMI |
The removable LCD panel |
|
|
Dimensions |
Take the 10 points module as an example. The 20 points modules share the same width and height, the only one difference exists in the length. |
|
Type |
Dimensions(mm) |
10 points main module |
71.6*90.4*51.3 |
20 points main module |
126.4*90.4*51.3 |
|
Introducing the FAB Intelligent Controller Series: a revolutionary new programmable controller proudly introduced by ARRAY. This state-of-the-art innovation utilizes FBD (Function Block Diagram) programming, offering a user-friendly and accessible alternative to the traditional PLC methods of ladder diagrams and instruction sets. ARRAY's visionary design concept for the FAB series seamlessly merges the time-tested PLC controller with a built-in writer, enabling direct programming via intuitive function keys located on the sleek LCD front panel. This ingenious integration significantly reduces costs while maximizing user convenience. Crafted with a compact and lightweight design, the ARRAY FAB is ideally suited for internal installation, ensuring it meets the demands of modern industrial environments effortlessly.
Moreover, the FAB Intelligent Controller Series elevates connectivity to new heights, offering both local and remote Internet communication and monitoring capabilities. The FAB seamlessly integrates with a voice module, empowering it to execute telephone remote control, voice prompting, auto-dialing, and a host of other advanced functions. Presently, the ARRAY FAB finds extensive applications across diverse sectors such as industry, agriculture, and automated home control systems. Its versatility ensures it can be utilized in virtually any setting, delivering unprecedented control and efficiency.
3af33c41