Technical Parameters |
Item |
AF-10MR-A2 |
AF-10MR-D2 |
AF-10MR-E2 |
AF-10MT-D2 |
AF-10MT-GD2 |
AF-10MT-E2
|
AF-20MR-A2
|
AF-20MR-D2
|
AF-20MR-E2
|
AF-20MT-D2
|
AF-20MT-GD2
|
AF-20MT-E2
|
Surge Immunity |
2kv(common mode), 1kv(differential mode), Level 3 (IEC61000-4-5) |
Electrostatic Discharge (outer casing) |
±8kv(air discharge)/±6kv(contact discharge), Level 3 (IEC61000-4-5) |
Ambient Temperature |
-10ºC~+55ºC |
Storage Temperature |
-40ºC~+70ºC |
Ambient Humidity |
5%~95%RH |
Degree of Protection |
IP20(Non-waterproof) |
Installation |
Fixing with M3 screws or Standard DIN rail mounting |
Dimensions (mm) |
71.6*90.4*51.3(10 points);126.4*90.4*51.3(20 points) |
Programming Language |
FBD |
Points |
10 points/20 points |
Memory Capacity |
127 FBDs |
Real-time Clock |
160h |
Password Protection |
yes |
Analog Operation |
At most 12 channels with DC 0-10V voltage |
Simulate Monitoring |
Yes |
Communication Interface |
support 2 channel with RS485 and 1 channel with program interfaces |
Baud Rate |
9600bps/19200bps |
Communication Protocol |
Self-defined protocol/MODBUS RTU protocol (only read) |
Power Supply |
Rated Voltage |
AC100-240V |
DC12-24V |
AC/DC12-24V |
DC12-24V |
DC12-24V |
DC12-24V
|
Permissible Range |
DC85-260V |
DC10-28V |
AC/DC10-28V |
DC10-28V |
DC10-28V |
DC10-28V
|
Power Consumption |
<10w
|
<7w
|
<7w
|
<2w
|
<2w
|
<2w
|
Digital Input |
Input Type |
NPN/PNP |
NPN/PNP |
NPN/PNP |
NPN/PNP |
NPN/PNP |
NPN/PNP
|
Input Signal 0 |
AC0-40V |
DC0-5V |
AC/DC0-5V |
DC0-5V |
DC0-5V |
DC0-5V
|
Input Signal 1 |
AC80-240V |
DC10-24V |
AC/DC10-24V |
DC10-24V |
DC10-24V |
DC10-24V
|
Isolation |
Photoelectric isolation |
-- |
-- |
-- |
-- |
--
|
Isolated Group |
6/12 groups |
Isolated Voltage |
2500/5000Vr.m.s |
Digital Output |
Output Type |
Relay |
Relay |
Relay |
Transistor(NPN) |
Transistor(PNP) |
Transistor(NPN) |
Isolation Method |
Relay isolation |
Relay isolation |
Relay isolation |
- |
- |
- |
Analog Input |
Input Type |
-- |
(DC0-10V)/6 inputs |
--
|
(DC0-10V)/6 inputs |
(4-20mA)/2 inputs |
-- |
(DC0-10V)/12 inputs
|
(DC0-10V)/12 inputs
|
(DC0-10V)/12 inputs
|
|
|
|
|
|
|
|
|
|
|
|
Type
|
AF-10MR-A2 |
AC100V-240V |
6 points digital input |
4 points relay output |
AF-10MR-D2 |
DC12V-24V |
6 points digital input (can be used as analog inputs) |
4 points relay output |
AF-10MR-E2 |
AC/DC12V-24V |
6 points digital input |
4 points relay output |
AF-10MT-D2 |
DC12V-24V |
6 points digital input (can be used as analog inputs) |
4 points NPN transistor output |
AF-10MT-GD2 |
DC12V-24V |
6 points digital input (can be used as analog inputs) |
4 points PNP transistor output
|
AF-10MT-E2 |
DC12V-24V |
6 points digital input |
4 points NPN transistor output |
AF-20MR-A2 |
AC100V-240V |
12 points digital input |
8 points relay output |
AF-20MR-D2 |
DC12V-24V |
12 points digital input (can be used as analog inputs) |
8 points relay output |
AF-20MR-E2 |
AC/DC12V-24V |
12 points digital input |
8 points relay output |
AF-20MT-D2 |
DC12V-24V |
12 points digital input (can be used as analog inputs) |
8 points NPN transistor output |
AF-20MT-GD2 |
DC12V-24V |
12 points digital input (can be used as analog inputs) |
8 points PNP transistor output
|
AF-20MT-E2 |
DC12V-24V |
12 points digital input |
8 points NPN transistor output |
|
Auxiliary Module |
AF-2322 |
the cable is used to read/write the program by PC 232 port |
AF-DUSB2 |
the cable is used to read/write the program by PC USB port |
AF-HMI |
The removable LCD panel |
|
|
Dimensions |
Take the 10 points module as an example. The 20 points modules share the same width and height, the only one difference exists in the length. |
|
Type |
Dimensions(mm) |
10 points main module |
71.6*90.4*51.3 |
20 points main module |
126.4*90.4*51.3 |
|
Introducing the FAB Intelligent Controller Series - a cutting-edge programmable controller brought to you by ARRAY. This revolutionary series simplifies the programming process through the intuitive Function Block Diagram (FBD) methodology, offering an ease of learning and use unparalleled by traditional PLC systems that rely on complex ladder diagrams and instructions. The innovative design philosophy of the ARRAY FAB series seamlessly integrates the capabilities of a conventional PLC with an inbuilt writer, empowering users to craft programs directly via function keys on the sleek LCD front panel. This advancement not only slashes costs but also significantly enhances user convenience. The ARRAY FAB is meticulously engineered to be compact and lightweight, making it an ideal choice for seamless internal installation.
Moreover, the FAB Intelligent Controller Series excels in connectivity, enabling both local and remote Internet communication and monitoring. It stands out with its compatibility with voice modules, facilitating telephone remote control, voice prompting, auto-dialing, and a host of other dynamic functions. Presently, the ARRAY FAB proves its versatility and excellence across a myriad of applications in sectors including industry, agriculture, and automated home control. Its adaptability ensures it can find a place virtually anywhere, enhancing efficiency and control in any environment.
87ef063e